首页> 外文会议>Information Technology, Networking, Electronic and Automation Control Conference >Study on Fault Analysis and Preventive Measures of Single-phase Grounding in low Current Grounding of Distribution System
【24h】

Study on Fault Analysis and Preventive Measures of Single-phase Grounding in low Current Grounding of Distribution System

机译:配电系统小电流接地单相接地故障分析及预防措施研究

获取原文

摘要

The neutral point of medium voltage distribution system generally adopts the method of low current grounding to ensure the power supply reliability. This paper makes a theoretical analysis of the single-phase grounding fault of the distribution system with ungrounded neutral and ungrounded via arc suppression coil, and makes a detailed simulation analysis of the single-phase grounding fault in the distribution network system of a 35kV substation with ungrounded neutral and four 10kV outgoing lines. The variation of fault point current, three-phase voltage and current, and zero sequence voltage current during the single-phase grounding of 10kV outgoing line and the grounding via different transition resistances are obtained quantitatively. The preventive measures to reduce the occurrence frequency of such faults are given. The conclusion of this paper is of certain reference value to relevant workers in power industry.
机译:中压配电系统中性点一般采用小电流接地方式,以确保电源的可靠性。本文对中性点未接地,消弧线圈不接地的配电系统单相接地故障进行了理论分析,并对一台35kV变电站配电网系统中的单相接地故障进行了详细的仿真分析。不接地的中性线和四根10kV出线。定量获得了10kV出线单相接地和不同过渡电阻接地时故障点电流,三相电压电流和零序电压电流的变化情况。提出了减少此类故障发生频率的预防措施。本文的结论对电力行业相关人员具有一定的参考价值。