首页> 外文会议>IEEE/IAS Industrial Commercial Power Systems Technical Conference >Impact of Sub Synchronous Resonance on operation of protective relays and prevention method
【24h】

Impact of Sub Synchronous Resonance on operation of protective relays and prevention method

机译:次同步谐振对继电保护动作的影响及预防方法

获取原文

摘要

Synchronous Resonance (SSR) is a phenomenon in which electrical energy is exchanged between generators and transmission systems below power frequency. It can be caused due to interaction of a series compensated transmission line with a generator; in addition, results in oscillation in the shaft and power swing. SSR causes increasing the magnitudes of voltage and current consequently occurrence of ferroresonance. It is obviously clear that protective relays are affected in such conditions. Although SSR is damped by FACTS devices protective relays must be adaptive to prevent mal operation independently. In this paper, Manitoba Hydro electrical network with series capacitors is simulated to investigate impact of SSR on operation of overcurrent relay. Ferroresonance occurs in most SSR conditions. Hence, in order to distinguish protection of hydro generator against sub harmonics, which interact with natural frequencies of the rotor; in addition, increasing reliability and security of protection a logical SSR detection algorithm based on sub harmonic measurement and ferroresonance analysis in time domain is proposed for overcurrent relay and examined in the network.
机译:同步共振(SSR)是一种现象,在该现象下,发电机和输电系统之间的电能在低于工频的情况下进行交换。这可能是由于串联补偿的传输线与发电机的相互作用引起的。此外,还会导致轴振动和动力摆幅。 SSR导致电压和电流的幅度增加,从而导致铁磁谐振的发生。显然,在这种情况下保护继电器会​​受到影响。尽管FACTS设备会抑制SSR,但必须对保护继电器进行自适应调整,以独立防止误操作。本文通过模拟串联电容器的曼尼托巴水电网络,研究了SSR对过电流继电器运行的影响。在大多数SSR条件下都会发生铁磁谐振。因此,为了区分水力发电机免受次谐波的影响,次谐波与转子的固有频率相互作用;此外,为提高保护的可靠性和安全性,提出了一种基于亚谐波测量和时域铁磁谐振分析的逻辑SSR检测算法,用于过电流继电器并在网络中进行了研究。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号