Directional relaying during single-pole tripping using phase-change in negative sequence current

机译:使用负序电流的相变在单极跳闸期间进行方向继电器

获取原文

摘要

Single-pole tripping (SPT) operation imposes problem to many power network relaying schemes. In this paper the directional relaying issue for faults during SPT condition is addressed. Algorithms applying negative sequence components of fault voltage and current for directional relaying find limitation during SPT as the prefault signals also contain negative sequence components. This paper proposes a directional relaying algorithm during SPT using phase-change in negative sequence current. The proposed technique is an attractive option as it does not use the fault voltage signal in the decision process. The technique is evaluated using data simulated with EMTDC/PSCAD for single and double circuit lines and the performance of the algorithm is also evaluated.
机译:单极跳闸(SPT)操作给许多电网中继方案带来了问题。本文解决了SPT条件下故障的定向继电器问题。由于预故障信号还包含负序分量,因此在SPT期间将故障电压和电流的负序分量用于定向继电器的算法会发现局限性。提出了一种利用负序电流相变的SPT定向继电器。所提出的技术是一种有吸引力的选择,因为它在决策过程中不使用故障电压信号。使用EMTDC / PSCAD模拟的单回路和双回路线路的数据评估该技术,并评估算法的性能。