This paper examines the problem of monitoring long-term voltage instability from a PMU installed at any transmission bus. It is shown that the well known impedance matching condition on a radially connected load bus, as well as the Local Identification of Voltage Emergency Situations (LIVES) method based on LTC transformers can be generalized into a New LIVES Index (NLI) suitable for any transmission bus feeding a weak area of a system. Results on an IEEE voltage stability test system validate the dependability and security of the new index for the early detection of voltage instability. Moving average, as well as a new filtering method based on short-time Fourier transform are employed to reduce the effect of noise and short-term transients.
机译:本文研究了从任何传输总线上安装的PMU监视长期电压不稳定性的问题。结果表明,径向连接的负载总线上众所周知的阻抗匹配条件,以及基于LTC变压器的电压紧急情况的本地识别(LIVES)方法,都可以推广为适用于任何传输的新LIVES索引(NLI)。总线为系统的薄弱区域供电。 IEEE电压稳定性测试系统上的结果验证了新指标的可靠性和安全性,可以尽早发现电压不稳定性。移动平均以及基于短时傅立叶变换的新滤波方法被用来减少噪声和短期瞬变的影响。