首页> 外文会议>IEEE India International Conference on Power Electronics >Modeling and Investigation of Insulation Defects by Partial Discharge in HV XLPE Cable
【24h】

Modeling and Investigation of Insulation Defects by Partial Discharge in HV XLPE Cable

机译:高压交联聚乙烯电缆局部放电绝缘缺陷的建模与研究

获取原文

摘要

Partial discharge (PD) analysis is a reliable diagnostic tool to assess the integrity and the quality of electrical insulation of power systems. Cable, insulator, bushing, power transformer, and other related parts of electrical equipment are used in the power system network. Spherical void in the insulation of the high voltage cable is assumed as origin of partial discharge (PD) and it may lead to heavy damage to the insulating system. This paper presents experimental PD test measurements as a function of void size, applied voltage and three capacitor type models for partial discharge simulation using MATLAB Simulink for 11 kV cross-linked polyethylene (XLPE) cable with void by implementing the standard PD model. For detection the imperfect XLPE insulation, the partial discharge detection method is used. The initiation of PD pulses in 11kV high voltage XLPE cable is presented with charge waveform and resulting PD pulses.
机译:局部放电(PD)分析是一种可靠的诊断工具,可以评估电力系统的电气绝缘的完整性和质量。电力系统网络中使用电缆,绝缘子,套管,电源变压器和电气设备的其他相关部件。高压电缆绝缘中的球形空隙被认为是局部放电(PD)的起源,它可能导致绝缘系统严重损坏。本文通过实施标准PD模型,针对11 kV交联聚乙烯(XLPE)带有空隙的电缆,使用MATLAB Simulink介绍了实验PD测试测量值与空隙尺寸,施加电压和三种电容器类型模型的关系,这些模型用于使用MATLAB Simulink进行局部放电仿真。为了检测不完美的XLPE绝缘,使用了局部放电检测方法。通过充电波形和产生的PD脉冲介绍了11kV高压XLPE电缆中PD脉冲的启动。