Nowadays, with the presence of Distributed Generators (DGs) in the medium voltage (MV) networks, the false tripping problem can occur to traditional overcurrent protections. Directional relay is a solution. To reduce the cost, a principle for the directional relay using only current measurements, which is based on symmetrical components method, was proposed and tested with simulations in case of Inverter-Interfaced DGs [1]. Calculated from the sequence currents, both the I2/I1 and ΔI2/ΔI1 ratios created two separate areas on the complex plane from which upstream or downstream faults could be easily determined. However, in case of Synchronous Generators, these two areas become so close that they can overlap each other. Hence the overlap causes some errors in the directional algorithm. In this paper, optimal boundaries for separating the two areas are studied. The algorithm shows good performances in most situations with these boundaries defined by Support Vector Machine technique.
机译:如今,随着中压(MV)网络中分布式发电机(DG)的出现,传统的过电流保护可能会出现误跳闸问题。定向继电器是一种解决方案。为了降低成本,提出了一种仅使用电流测量的定向继电器原理,该原理基于对称分量法,并在逆变器接口DG的情况下进行了仿真测试[1]。从顺序电流计算,I2 / I1和ΔI2/ΔI1比率均在复平面上创建了两个独立的区域,从中可以轻松确定上游或下游故障。但是,在使用同步发电机的情况下,这两个区域变得如此紧密,以至于它们可以相互重叠。因此,重叠会在定向算法中引起一些错误。在本文中,研究了将两个区域分开的最佳边界。通过支持向量机技术定义的这些边界,该算法在大多数情况下均表现出良好的性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号