A comparison between frequency relays and vector surge relays for synchronous DG anti-islanding protection

机译:同步DG防孤岛保护的频率继电器和矢量浪涌继电器的比较

获取原文
获取原文并翻译 | 示例

摘要

Investigations show that reactive power mismatch affects frequency relays performances. Vector surge relays (VSRs) being frequency based relays are widely used for islanding detection in power systems. Considering similarities between frequency relays'(FRs') and VSRs' performances, it is suggested that FRs can detect islanding conditions as well as VSRs, however no evidence is presented for comparing FR and VSR performances in case of reactive power mismatch. This paper presents a comparison of FR and VSR islanding detection protection performances considering reactive power mismatch. The results confirm the validity of replacing VSRs with FRs.
机译:调查表明,无功功率不匹配会影响频率继电器的性能。矢量电涌继电器(VSR)是基于频率的继电器,已广泛用于电力系统中的孤岛检测。考虑到频率继电器(FRs)和VSRs性能之间的相似性,建议FRs可以检测孤岛条件和VSR,但是在无功功率不匹配的情况下,没有证据表明可以比较FR和VSR性能。本文介绍了考虑无功功率不匹配的FR和VSR孤岛检测保护性能的比较。结果证实了用FR代替VSR的有效性。