Under frequency load shedding schemes in systems with high PV penetration: Impact and improvements

机译:PV渗透率高的系统中的低频减载方案:影响和改进

获取原文
获取外文期刊封面目录资料

摘要

With the increasing integration of renewable energies in the power system a thorough analysis of the adequacy of defence plans is needed. This paper focusses on the impact of a high penetration of photovoltaics in distribution systems on the under frequency load shedding schemes designed by the TSO. First an overview of the issues arising from a higher penetration of embedded renewable energy sources in the current UFLS scheme design is described. It will be shown that neglecting photovoltaics in load shedding scheme design can lead to adverse effects in system stability and can have a disproportional high social impact. Subsequently an overview of different methodologies to improve the UFLS scheme design is given. These methodlogies are then applied to the measurements of two feeders in the Belgian power system. From the evaluation of these results, it can be concluded that the proposed methodologies lead to substantial improvements in UFLS scheme adequacy.
机译:随着可再生能源在电力系统中的集成度不断提高,需要对防御计划的充分性进行全面分析。本文关注的是配电系统中光伏的高渗透率对TSO设计的低频减载方案的影响。首先,概述了当前UFLS方案设计中嵌入式可再生能源的更高渗透率所引起的问题。将表明,在减载方案设计中忽略光伏发电会导致系统稳定性受到不利影响,并可能产生不成比例的高度社会影响。随后概述了改进UFLS方案设计的不同方法。然后将这些方法应用于比利时电力系统中两个馈线的测量。通过对这些结果的评估,可以得出结论,所提出的方法论导致UFLS计划充分性的实质性改进。