UHF Partial discharge (PD) detection in MV transformers is discussed in this paper. Transformers are modeled as resonant cavities and bushing openings as slot antennas. Laboratory tests are carried out to validate the models. At first, irradiation properties are determined placing emitting dipoles inside a dummy transformer tank and detecting the electromagnetic emission through appropriate antennas. Then, CAD simulations are done showing good fitting with experimental results. At last, simulations and PD measurements are carried out on a three-phase 15 kV transformer in order to find the optimum detection bandwidth and develop suitable PD sensors.
机译:本文讨论了中压变压器中的UHF局部放电(PD)检测。变压器建模为谐振腔,套管开口建模为缝隙天线。进行实验室测试以验证模型。首先,确定辐射特性,将发射偶极子放置在虚拟变压器箱内,并通过适当的天线检测电磁辐射。然后,进行了CAD仿真,显示与实验结果非常吻合。最后,在三相15 kV变压器上进行仿真和局部放电测量,以找到最佳的检测带宽并开发合适的局部放电传感器。