Experimental results of the thermal and hydraulic performances of silicon-based, low aspect ratio micro-pin-fin cold plates under cross flow conditions are reported. The pins were both circular and square in shape with dimensions (diameter for circular and sides for square) ranging from 50 to 150 μm. The test chip contained 20 integral 75x75 μm temperature sensors which were used to determine the thermal resistance (K W~(-1)) of the cold plates. The experiments were conducted using water, over a Reynolds number (Re) ranging from 40 to 1000. The data show that the average Nusselt number (Nu) based on the fin diameter varies as Re~(0.84) for Re < 100 and as Re~(0.73) for Re > 100 , where Re is the Reynolds number based on maximum velocity and the fin diameter. Analysis of the Fanning friction factor (f) data shows that f varies as Re~(-1.35) for Re < 100 and as Re~(-0.1) for Re > 100.
机译:报道了在错流条件下硅基低纵横比微针翅式冷板的热性能和水力性能的实验结果。销的形状为圆形和正方形,其尺寸(圆形的直径和正方形的侧面)的范围为50至150μm。测试芯片包含20个集成的75x75μm温度传感器,用于确定冷板的热阻(K W〜(-1))。实验是在水上进行的,雷诺数(Re)在40到1000之间。数据表明,基于鳍片直径的平均Nusselt数(Nu)在Re <100和Re <100时变化为Re〜(0.84)。 Re> 100时为〜(0.73),其中Re是基于最大速度和鳍片直径的雷诺数。对Fanning摩擦因数(f)数据的分析表明,对于Re <100,f随Re〜(-1.35)变化,对于Re> 100随Re〜(-0.1)变化。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号