PD measurement and commissioning test for cables

机译:电缆的局放测量和调试测试

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

The enhancement of AC commissioningrntests lies in partial discharge measurements. KEMArnhas developed a system for PD measurements to berncombined with their series resonant test set. Arncombination of instruments have been selectedrnresulting in a good signal-to-noise ratio. Thisrnequipment comprises a coupling capacitor withrnquadrupole and an advanced measuring instrument asrndetector.rnField experience so far has shown an average noisernlevel of 20pC. The calibration of these measurementsrnis based on the use of a 'traditional' calibrator. Thernattenuation in power cables results in an uncertaintyrnrelated to this calibration factor. Therefore, thernmaximum length which can be measured is 3 to 4km.rnAlthough it is not always possible to exclude allrnpossible disturbances, various measures can (andrnshould) be taken to prevent corona from disturbing thernmeasurements.
机译:AC调试测试的增强之处在于局部放电测量。 KEMArn已经开发了一种用于PD测量的系统,该系统可以与他们的串联谐振测试仪结合使用。已经选择了仪器的组合,从而产生了良好的信噪比。该设备包括一个带有四极的耦合电容器和一个先进的测量仪器asrndetector。到目前为止,现场经验表明平均噪声水平为20pC。这些测量的校准基于“传统”校准器的使用。电力电缆的衰减会导致与此校准系数有关的不确定性。因此,可以测量的最大长度为3至4 km。尽管不一定总能排除所有可能的干扰,但可以(应)采取各种措施来防止电晕干扰测量。