The Green Data Center Project was a successful effort to significantly reduce the energy use of the National Snow and Ice Data Center (NSIDC). Through a full retrofit of a traditional air conditioning system, the cooling energy required to meet the data center's constant load has been reduced by over 70% for summer months and over 90% for cooler winter months. This significant change is achievable through the use of airside economization and a new indirect evaporative cooling system. One of the goals of this project was to create awareness of simple and effective energy reduction strategies for data centers. This project's geographic location allowed maximizing the positive effects of airside economization and indirect evaporative cooling, but these strategies may also be relevant for many other sites and data centers in the U.S.
机译:绿色数据中心项目是一项成功的工作,旨在显着减少国家冰雪数据中心(NSIDC)的能源消耗。通过对传统空调系统的全面改造,满足数据中心恒定负载所需的冷却能量在夏季减少了70%以上,在冬季凉爽的月份减少了90%以上。通过使用节省空气的区域和新的间接蒸发冷却系统,可以实现这一重大变化。该项目的目标之一是提高人们对数据中心简单有效的节能战略的认识。该项目的地理位置可以最大程度地实现节省空侧和间接蒸发冷却的积极效果,但是这些策略可能也与美国的许多其他站点和数据中心相关。