首页> 外文会议>Fire and Materials 2013 >CONE CALORIMETER TESTS OF WOOD COMPOSITES
【24h】

CONE CALORIMETER TESTS OF WOOD COMPOSITES

机译:木材复合材料的锥形量热测试

获取原文
获取原文并翻译 | 示例

摘要

The cone calorimeter is widely used for the determination of the heat release rate (HRR) ofrnbuilding products and other materials. As part of an effort to increase the availability of conerncalorimeter data on wood products, the U.S. Forest Products Laboratory and the American WoodrnCouncil conducted this study on composite wood products in cooperation with the Composite PanelrnAssociation and APA-The Engineered Wood Association. We tested the specimens in accordancernwith ASTM E 1354 and used a heat flux of 50 kW/m~2. The twenty-nine commercial woodrncomposites included untreated and fire-retardant-treated (FRT) particleboards, untreated and FRTrnmedium density fiberboards, untreated high density fiberboards, untreated plywoods, and untreatedrnoriented strand boards. Such FRT composites are made to have a Class A flame spread rating whenrntested in the ASTM E 84 tunnel test. Fire retardant treatment of the wood products reduced the initialrnHRR, reduced the mass loss rate, increased the residual mass fraction, resulted in lower averagerneffective heat of combustion values, and usually resulted in longer ignition times. For the untreatedrnspecimens, the results for residual mass fraction at the end of the test ranged from 0.13 to 0.28 with arnmean result of 0.23. In contrast, the results for the FRT samples ranged from 0.33 to 0.39 with a meanrnresult of 0.36. In the case of the 300 s HRR averages, the range was 118 to 218 kW/m~2 for thernuntreated composites and 58 to 100 Kw/m~2 for the FRT composites.
机译:锥形量热仪广泛用于确定建筑产品和其他材料的热释放率(HRR)。为了提高木材产品的电量仪数据的可用性,美国林产品实验室和美国伍德恩委员会与复合材料面板协会和APA(工程木材协会)合作对复合木材产品进行了这项研究。我们根据ASTM E 1354测试了样品,并使用了50 kW / m〜2的热通量。 29种商用木复合材料包括未处理和阻燃处理(FRT)的刨花板,未处理和FRT中密度纤维板,未处理的高密度纤维板,未处理的胶合板和未处理的取向刨花板。当在ASTM E 84隧道测试中进行测试时,此类FRT复合材料被制成具有A级火焰蔓延等级。木质产品的阻燃处理降低了初始HRR,降低了质量损失率,增加了残留质量分数,导致平均燃烧有效热值降低,通常导致更长的点火时间。对于未经处理的样品,在测试结束时残留质量分数的结果在0.13至0.28的范围内,平均值平均值为0.23。相反,FRT样品的结果范围为0.33至0.39,平均结果为0.36。在300 s HRR平均值的情况下,未经处理的复合材料的范围为118至218 kW / m〜2,而FRT复合材料的范围为58至100 Kw / m〜2。

著录项

  • 来源
    《Fire and Materials 2013》|2013年|401-412|共12页
  • 会议地点 San Francisco CA(US);London(GB)
  • 作者单位

    Forest Service Forest Products Laboratory, USA;

    rnAmerican Wood Council, USA;

  • 会议组织
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

相似文献