Previously published research findings [1] on the impact of tap changer position on the steady state performance of distribution networks indicate that very little impact results from varying the tap changer position. In this paper, a similar investigation is carried out, but on a network with very high voltage transmission lines operating in parallel with a well-developed corridor of 400kV lines. The per-unit impedance of a line is reduced drastically as the line voltage is increased. When the design voltage of the transmission lines is high, the transformer impedance becomes dominant and plays a key role in the system. This paper investigates the effect of varying the impedance of a 765/400kV transformer on the steady-state (loadflow and active power losses) and voltage stability of the Cape corridor.
机译:先前发表的有关分接开关位置对配电网络稳态性能影响的研究结果[1]表明,改变分接开关位置几乎不会产生影响。在本文中,进行了类似的研究,但是在具有非常高电压的输电线路并与发达的400kV线路走廊并行运行的网络上。随着线路电压的增加,线路的单位阻抗会大大降低。当传输线的设计电压较高时,变压器阻抗将占主导地位,并在系统中起关键作用。本文研究了改变765 / 400kV变压器的阻抗对Cape走廊的稳态(潮流和有功功率损耗)和电压稳定性的影响。