首页> 外文会议>Electrical Insulation (ISEI), Conference Record of the 2012 IEEE International Symposium on >Experiences with commissioning testing of HV EHV cable systems: The influence of voltage level and duration for identifying life limiting defects
【24h】

Experiences with commissioning testing of HV EHV cable systems: The influence of voltage level and duration for identifying life limiting defects

机译:高压和超高压电缆系统调试测试的经验:电压水平和持续时间对确定使用寿命限制缺陷的影响

获取原文
获取原文并翻译 | 示例

摘要

Over the last decade and a half, thousands of kilometres of installed XLPE HV and EHV cable systems have been subjected to after-laying commissioning testing prior to energization. The commissioning test usually consists of a combination of AC HiPot & Partial Discharge (PD) testing. PD testing, in particular, has gained acceptance as a valid diagnostic tool for condition assessment of cable insulation. It is well known and understood that the results obtained from a partial discharge test depend not only on the conditions under which the test was performed but also on the test equipment itself including the type of sensor used and its location. Relying on experienced gained with AC Withstand and PD commissioning testing of more than 2,100 km of HV & EHV cable systems the paper examines the influence of voltage source and withstand duration of the withstand test for successfully identifying life limiting defects in newly laid HV & EHV Cable systems both in terms of breakdown and also in terms of detection of partial discharge sources from the same defects. The paper further provides statistical summary of tests performed on more than 2100 km of HV and EHV cable systems including failure rates of accessories and PD occurrence rates. The paper also provides several case studies of PD detected in cable accessories during AC HiPot commissioning testing.
机译:在过去的十五年中,已安装的数千公里XLPE HV和EHV电缆系统在通电前已进行了铺设后的调试测试。调试测试通常包含AC HiPot和局部放电(PD)测试的组合。特别是,局部放电测试已被接受为用于电缆绝缘状况评估的有效诊断工具。众所周知,从局部放电测试中获得的结果不仅取决于进行测试的条件,还取决于测试设备本身,包括所用传感器的类型及其位置。依靠在超过2,100 km的HV&EHV电缆系统的交流耐受和PD调试测试中获得的经验,本文研究了电压源的影响和耐受测试的持续时间,以成功识别新铺设的HV&EHV电缆中的使用寿命限制缺陷不仅在故障方面,而且在检测来自相同缺陷的局部放电源方面。本文进一步提供了在2100 km以上的HV和EHV电缆系统上进行的测试的统计摘要,包括附件的故障率和PD的发生率。本文还提供了一些案例研究,这些案例研究是在AC HiPot调试测试期间在电缆附件中检测到的PD。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号