The tracking voltage in the inclined plane test with AC is compared to the tracking voltage with DC, using the initial-tracking-voltage test method as per ASTM D2303 and a proposed coefficient of variation parameter. The severity of DC, as opposed to AC voltage, on RTV silicone rubber materials is confirmed using both strategies, where +DC is found to be the most severe voltage. The leakage current waveforms are found to consist of two components corresponding to wetting of the surface and to dry-band arcing. The mean value of the leakage current is a reflection of the wetting of the surface; whereas, the leakage current variation is a reflection of the dry-band arcing. Accordingly, a coefficient of variation parameter is proposed as an indicator of the relative severity of the dry band-arcing. Employing this coefficient of variation parameter, the ratios of the equivalent +DC and -DC to AC initial-tracking voltage are attained for 30 wt% silica filled two-part RTV silicone rubber. The results obtained using the coefficient of variation parameter have been verified experimentally using the initial-tracking-voltage in ASTM D2303.
机译:使用符合ASTM D2303的初始跟踪电压测试方法和建议的变化系数参数,将使用AC进行的倾斜平面测试中的跟踪电压与使用DC进行的跟踪电压进行比较。两种策略都证实了RTV硅橡胶材料上DC相对于AC电压的严重性,其中+ DC被认为是最严重的电压。发现泄漏电流波形由与表面润湿和干带电弧相对应的两个分量组成。泄漏电流的平均值反映了表面的润湿性。反之,漏电流变化是干带电弧的反映。因此,提出了变化系数参数作为干带飞弧的相对严重性的指标。利用该变化系数参数,对于30重量%的二氧化硅填充的两部分RTV硅橡胶,获得了等效的+ DC和-DC与AC的初始跟踪电压的比率。使用变异系数参数获得的结果已通过ASTM D2303中的初始跟踪电压进行了实验验证。