Proposed maintenance hipot levels for generator rotor windings

机译:发电机转子绕组的建议维护水平

获取原文
获取原文并翻译 | 示例

摘要

Hipot testing is always used as a factory or commissioning test to ensure that the groundwall insulation in new stator windings and wound rotor windings is fit for service. Maintenance hipot testing is also used by some motor and generator owners to periodically ensure that the insulation in windings that have been in operation will not fail when returned to service. The dc and ac hipot test levels for factory or commissioning tests are well established by IEEE/ANSI and IEC. Several standards also provide guidance on maintenance hipot tests for stator windings. However, there is no such guidance given for maintenance hipot tests of rotor windings. This paper reviews the standards applicable for generator rotor winding hipot testing, and highlights the lack of any guidelines by IEEE on test levels for generator rotors that have seen service. Since an important purpose of maintenance hipot testing is to ensure that the insulation can withstand voltage transients that can occur in operation, a review is made of the transient voltage stresses that the rotor ground insulation may see. Based on the transients that are possible, it is proposed that the rotor winding maintenance ac hipot test level for large machines be set to a minimum of 1000 Vac, rms, or half the final acceptance hipot (whichever is higher).
机译:耐压测试始终用作工厂测试或调试测试,以确保新定子绕组和绕线转子绕组中的接地绝缘适合使用。一些电动机和发电机的所有者还使用维护耐压测试,以定期确保已投入运行的绕组中的绝缘不会失效。 IEEE / ANSI和IEC很好地确定了工厂或调试测试的直流和交流电压测试水平。若干标准还提供了有关定子绕组的耐压测试的指南。但是,对于转子绕组的耐压测试没有给出这样的指导。本文回顾了适用于发电机转子绕组耐压测试的标准,并着重指出了IEEE对于已使用的发电机转子的测试水平缺乏任何指导原则。由于维护耐压测试的一个重要目的是确保绝缘体能够承受运行中可能发生的电压瞬变,因此对转子接地绝缘体可能会遇到的瞬态电压应力进行了审查。根据可能的瞬变,建议将大型机器的转子绕组维护交流耐压测试水平设置为最小值1000 Vac,有效值或最终可接受耐压的一半(以较高者为准)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号