首页> 外文会议>Electrical Insulation (ISEI), Conference Record of the 2012 IEEE International Symposium on >Emission and propagation mechanisms of PD pulses for UHF and traditional electrical measurements
【24h】

Emission and propagation mechanisms of PD pulses for UHF and traditional electrical measurements

机译:用于UHF和传统电测量的PD脉冲的发射和传播机制

获取原文
获取原文并翻译 | 示例

摘要

Partial Discharge (PD) measurements are considered as a very powerful technique for testing and monitoring the condition of high-voltage (HV) insulations. PD activity is generally accepted as an early breakdown indicator, which is also reflected in numerous standards. In the present contribution, the authors describe the fundamentally different propagation mechanisms of electrical impulses in the conventional (according IEC 60270) and the ultra-high frequency (UHF) range. The low-frequency components of the PD signals propagate mainly via the conductor, whereas the high-frequency components (UHF signals) are radiated as electromagnetic waves. The sensitivity and spectrum of the measurement depends strongly on the geometric position of the PD, damping and resonances of the propagation path, and the frequency response of the receiver. Field simulation has been used as an appropriate tool for calculating PD signal propagation in HV apparatus.
机译:局部放电(PD)测量被认为是用于测试和监视高压(HV)绝缘状况的非常强大的技术。 PD活动通常被认为是早期分解指标,这也反映在许多标准中。在目前的贡献中,作者描述了在常规(根据IEC 60270)和超高频(UHF)范围内电脉冲的根本不同的传播机制。 PD信号的低频分量主要通过导体传播,而高频分量(UHF信号)则作为电磁波辐射。测量的灵敏度和频谱在很大程度上取决于PD的几何位置,传播路径的阻尼和谐振以及接收器的频率响应。现场模拟已被用作计算高压设备中PD信号传播的合适工具。