The self-extinguishing current limit and the arc-burning time of compensated 20-kV-power-grids

机译:补偿20 kV电网的自熄电流极限和燃弧时间

获取原文
获取原文并翻译 | 示例

摘要

The actual valid self-extinguishing current limit of 20-kV-compensated power grids, written in the VDE 0228 is 60 A. This limit is based on trials from the years 1963 done by M. Erich und H. Heinze. In the year 1981 K. H. Koch presented results of new earth-fault trials. He concluded that the self-extinguishing current increases for larger power grids. An afresh scientific interpretation of both experiments leads to a novel proposal for a self-extinguishing current limit for compensated 20-kV-power-grids. This novel self-extinguishing current limit would allow the extension of current compensated power grids. Further the medium arc-burning time for compensated power grids is discussed.
机译:在VDE 0228中写入的20 kV补偿电网的实际有效自熄电流极限为60A。该极限基于M. Erich und H. Heinze从1963年开始的试验。 1981年,K。H. Koch提出了新的接地故障试验结果。他得出结论,大型电网的自熄电流会增加。对这两个实验的全新科学解释导致提出了一种新的提议,要求对补偿后的20 kV电网自熄灭电流。这种新颖的自熄电流限制将允许扩展电流补偿电网。进一步讨论了补偿电网的中等电弧燃烧时间。