首页> 外文会议>Disinfection and reuse symposium 2018: linking water quality and public health >Bayonne, NJ Combined Sewer Overflow Treatment Demonstration Project: Disinfection Results
【24h】

Bayonne, NJ Combined Sewer Overflow Treatment Demonstration Project: Disinfection Results

机译:新泽西州巴约讷市下水道溢流联合处理示范项目:消毒结果

获取原文
获取原文并翻译 | 示例

摘要

A CSO pilot treatment program has been completed in Bayonne, New Jersey. The project focused on verifying performance of selected technologies for TSS removal and disinfection under field conditions. Following pretreatment for TSS removal in several alternative processes, the effluent was disinfected with peracetic acid (PAA) or ultraviolet (UV) light utilizing low-pressure and medium-pressure lamps. The test units had a design capacity of between 189 and 3,785 L/min (50 to 1,000 gpm) and were fed from an extensive CSO catchment area. PAA effectiveness was a function of the dose applied as normalized by COD for E. coli, fecal coliforms and Enterococci. Three (3) log reduction (deactivation) was achieved, on average, at 0.010 mg/L PAA dose per mg/L of COD present. Similar deactivation was achieved by UV dose of 25 mJ/cm~2 for low-pressure UV system and by 40 mJ/cm~2 for medium-pressure system.
机译:新泽西州巴约讷市已完成一项公民社会组织试点治疗计划。该项目的重点是在野外条件下验证用于TSS去除和消毒的选定技术的性能。在几种替代方法中进行了去除TSS的预处理后,使用低压和中压灯用过氧乙酸(PAA)或紫外线(UV)对废水进行消毒。这些测试装置的设计能力在189至3,785升/分钟(50至1,000加仑/分钟)之间,并从广阔的CSO集水区进料。 PAA有效性是大肠杆菌,粪便大肠菌群和肠球菌的COD标准化剂量的函数。每存在1 mg / L的COD,平均三(3)个对数减少(失活)量为0.010 mg / L PAA剂量。低压紫外线系统的紫外线剂量为25 mJ / cm〜2,中压系统的紫外线剂量为40 mJ / cm〜2,实现了类似的失活。