首页> 外文会议>Compumag Conference on the Computation of Electromagnetic Fields vol.3; 20050626-30; Shenyang(CN) >Numerical Prediction of EMI on the Secondary DC Cable in Cable Tunnel Due to a Direct Lightning Strike in Substation
【24h】

Numerical Prediction of EMI on the Secondary DC Cable in Cable Tunnel Due to a Direct Lightning Strike in Substation

机译:变电站直接雷击引起的电缆隧道二次直流电缆EMI的数值预测

获取原文
获取原文并翻译 | 示例

摘要

In this paper, considering the location at infinity under the earth surface to be the zero-voltage reference point, the multi-conductor transmission lines (MTLs) theory is applied to model the secondary DC cable system in substation. Based on the FEM, the cable tunnel can be taken into account. As a result, both the current flowing in the cable shield and the transverse voltage between the cable core and the cable shield can be obtained. The results show that the injection position of the lightning current has great effect on the transient electromagnetic interference on the secondary cable.
机译:在本文中,考虑到地表下无限远处的位置为零电压参考点,将多导体传输线(MTL)理论应用于变电站的二次直流电缆系统建模。基于FEM,可以考虑电缆隧道。结果,可以获得在电缆屏蔽层中流动的电流以及在电缆芯与电缆屏蔽层之间的横向电压。结果表明,雷电流的注入位置对次级电缆上的瞬变电磁干扰有很大影响。