首页> 外文会议>Compressors 2009 >LOW PRESSURE SHOWERED EVAPORATOR IN ABSORPTION COOLING UNIT
【24h】

LOW PRESSURE SHOWERED EVAPORATOR IN ABSORPTION COOLING UNIT

机译:吸收式冷却装置中的低压低压蒸发器

获取原文
获取原文并翻译 | 示例

摘要

The article describes the subject of low pressure absorption cooling with pair of working fluids lithium bromide and water.It pursuits the design of heat exchangers in the unit and it targets on the influence of type of evaporator`s construction on the output of the whole unit.In graphs are shown measured values on small scale experimental unit with cooling power of 1kW.The application of showered heat exchanger in the evaporator of the cooling machine requires water circulation as primary cooling medium.Primary cycle is powered by circulation pump sucking water from evaporator and showering the exchanger.The exchanger has on its inner side cooled medium of secondary circuit which on its outer side cools down ambient air.The article discusses based on mathematical model theoretical possibilities of designing primary circuit and its influence on total effectiveness of cooling unit. rnThe results of these experiments serve as foundations for design and construction of experimental cooling unit with output of 10kW.
机译:本文介绍了使用一对工作流体溴化锂和水进行低压吸收式冷却的主题,它追求单元内热交换器的设计,并针对蒸发器的结构类型对整个单元输出的影响。图中显示了制冷功率为1kW的小型实验装置的测量值。花洒式换热器在冷却机的蒸发器中的应用需要水循环作为主要冷却介质。主循环由循环泵驱动,从蒸发器中吸水交换器在其内侧具有次级回路的冷却介质,该介质在其外侧冷却周围的空气。本文基于数学模型,讨论了设计初级回路的理论可能性及其对冷却装置总效率的影响。这些实验的结果为设计和建造功率为10kW的冷却装置的实验奠定了基础。

著录项

  • 来源
    《Compressors 2009》|2009年|p.1-4|共4页
  • 会议地点 Casta Papiernicka(SK);Casta Papiernicka(SK)
  • 作者

    Daniel ČURKA; Michal Molotta;

  • 作者单位

    STU Bratislava,Nám.Slobody 17,Bratislava,812 31,Slovakia daniel.curka@stuba.sk;

    I:E:systems spol s r.o.,Konopnául.38,Bratislava,820 15,Slovakia michal.molotta@iesystems.sk;

  • 会议组织
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 制冷工程;
  • 关键词