Study on Typical PD Models in High Voltage Oil-filled Cable

机译:高压充油电缆中典型PD模型的研究

获取原文
获取原文并翻译 | 示例

摘要

In High Voltage Oil-filled Cable, Partial discharge (PD) cause degradation of insulation system and a study of their behaviors can give useful information regarding the state of the insulation system. Partial discharge tests are therefore, carried out as quality checks for the insulation system. In this paper, several typical defect PD models in High Voltage Oil-filled Cable are designed. The PD graphs and discharge parameters are measured by a digital PD measuring system (TE571). Results show that the shape, distribution of discharge pulse and symmetry of PD graphs varied with discharge models. Due to their presentations to different models characteristics, four parameters, including Sk(Skewness), Ku(Kurtosis), cc (Correlation coefficient) and Asy(Asymmetry), are selected from the finger parameter set. This can be served as the reference of PD pattern recognition.
机译:在高压充油电缆中,局部放电(PD)会引起绝缘系统的性能下降,对其行为的研究可以为绝缘系统的状态提供有用的信息。因此,进行局部放电测试以作为绝缘系统的质量检查。本文设计了高压充油电缆中几种典型的缺陷PD模型。通过数字PD测量系统(TE571)测量PD图和放电参数。结果表明,放电脉冲的形状,分布和PD图的对称性随放电模型而变化。由于它们针对不同模型特征的呈现,因此从手指参数集中选择了四个参数,包括Sk(Skewness),Ku(Kurtosis),cc(Correlation coefficient)和Asy(Asymmetry)。这可以用作PD模式识别的参考。