It is difficult for existing HVDC line protections to distinguish internal fault from external fault rapidly and accurately, and the protective setting work encounters problems and difficulties. As a result, these protections have a low correct action rate. According to the feature of HVDC transmission system, this paper studies the characteristics of the natural boundary composed of the smoothing reactor and the DC filters. It is proved that this boundary has obvious differences in attenuation characteristics of different frequency components of fault transient signals. Consequently, a non-unit transient-based protection (NUTBP) is proposed. Wavelet multi-resolution signal decomposition technique is used to analyze the transient current caused by the faults. Extensive simulation results indicate that non-unit transient protection can clear all faults on the whole line quickly and credibly.
机译:现有的高压直流输电线路保护装置难以快速,准确地将内部故障与外部故障区分开,并且保护整定工作遇到问题和困难。结果,这些保护的正确动作率低。根据高压直流输电系统的特点,研究了由平滑电抗器和直流滤波器组成的自然边界的特性。证明了该边界在故障暂态信号的不同频率分量的衰减特性上有明显的差异。因此,提出了一种基于非单位暂态的保护(NUTBP)。小波多分辨率信号分解技术用于分析故障引起的暂态电流。大量的仿真结果表明,非单元暂态保护可以快速,可靠地清除整条线路上的所有故障。