摘要

Aiming at EHV transmission lines with shunt compensators, a novel technique is proposed to distinguish fault nature according to low frequency components in faulted phase current of reactor at the recovery voltage stage. In order to identify the magnitude of low frequency components, a energy function is defined which can determine the fault nature in 2~4 fundamental cycles rapidly and accurately. The characteristics of faulted phase current are analyzed in detail. For a permanent fault, the current contains power frequency and decaying slowly DC components. While for a transient fault, the current contains power frequency and low frequency components. Theoretical analysis and EMTP simulation prove that the proposed identification scheme can distinguish the fault nature exactly and improve the success rate of reclosure significantly.
机译:针对具有并联补偿器的超高压输电线路,提出了一种新技术,根据电抗器在恢复电压阶段的故障相电流中的低频分量来区分故障性质。为了识别低频分量的大小,定义了一个能量函数,该函数可以快速准确地确定2〜4个基本周期内的故障性质。详细分析了故障相电流的特性。对于永久性故障,电流包含电源频率和缓慢衰减的直流分量。对于瞬态故障,电流包含工频和低频分量。理论分析和EMTP仿真表明,提出的识别方案能够准确地区分故障性质,显着提高重合闸成功率。