首页> 外文会议>Asia-Pacific Power and Energy Engineering Conference;APPEEC >Measurement and Analysis on Electromagnetic Environment of 1000kV UHV AC Transmission Line
【24h】

Measurement and Analysis on Electromagnetic Environment of 1000kV UHV AC Transmission Line

机译:1000kV特高压交流输电线路电磁环境的测量与分析

获取原文

摘要

The electromagnetic environment of UHV project keeps a close relationship with the environment protection and project cost, so it would catch the full attention after its operation. To well research the electromagnetic environment level and discipline of UHV AC transmission line, a detailed test in the widen areas was carried out, including power frequency electric field, power frequency magnetic field and radio interference. The results showed that, the measurement values of power frequency electric and magnetic field were basically the same as theoretical calculation results. The distribution of radio interference was consistent with the calculation result, but there were differences in the quantity. The actual radio interference level was 2.5-4.5dB(μV/m) lower than the calculation result by CISPR generation function formula. By comparing with fair-weather and foul-weather, radio interference in the condition of fair-weather was 16-19dB (μV/m) less than that in light rainy day.
机译:特高压工程的电磁环境与环境保护和工程造价有着密切的关系,因此在运行后将引起人们的充分关注。为了深入研究特高压交流输电线路的电磁环境水平和规律,在广阔的领域进行了详细的测试,包括工频电场,工频磁场和无线电干扰。结果表明,工频电场和磁场的测量值与理论计算结果基本相同。无线电干扰的分布与计算结果一致,但数量存在差异。实际无线电干扰水平比CISPR生成函数公式的计算结果低2.5-4.5dB(μV/ m)。通过比较晴天和恶劣天气,晴天的无线电干扰比轻雨天少16-19dB(μV/ m)。