摘要

In this paper, the influence of grounding wire configuration of traction substation on observed transient overvoltage at some electric machines, those are diode rectifier, series reactor and so on, is experimentally measured. According to our previous experiences, a diode rectifier is the weakness against lightning and making the transient voltage smaller can increase the reliability of traction power supply system against lightning. Now, two grounding wires are installed separately at Ooi-Futo Substation. Throughout our experiments, by connecting them and by disconnecting the one end of grounding wire near the rectifier, it was confirmed that the transient voltage observed at diode rectifier could be decreased. In this paper, some experimental results will be explained in detail.
机译:本文通过实验测量了牵引变电站的接地线配置对观察到的某些电机的瞬态过电压的影响,这些电机包括二极管整流器,串联电抗器等。根据我们以前的经验,二极管整流器是防雷的弱点,减小瞬态电压可以提高牵引电源系统防雷的可靠性。现在,在Ooi-Futo变电站中分别安装了两条接地线。在我们的整个实验中,通过连接它们并断开整流器附近的接地线的一端,已确认可以减小在二极管整流器上观察到的瞬态电压。在本文中,将详细解释一些实验结果。