EXPERIMENTAL INVESTIGATION OF NON-CONDENSABLE GASES INFLUENCE ON CONDENSERS OPERATION OF HIGH-CAPACITY REFRIGERATING SYSTEM AT THE AMMONIA TERMINAL

机译:非冷凝气体的实验研究对氨气终端大容量制冷系统冷凝器运行的影响

获取原文
获取原文并翻译 | 示例

摘要

Operating conditions of high-capacity refrigerating system for ammonia terminal is highlyrninfluenced by non-condensable gases coming into the condensers. Experimental study of air-cooledrncondensers operation in the presence of high concentration of non-condensable gases is carried out.rnCharacteristic of non-condensable gases influence on the ammonia vapor condensation insidernhorizontal tubes are determined. Further results of mathematical modeling for ammonia vaporrncondensation in the presence of air inside horizontal tubes for various velocities of vapor-gasrnmixtures are presented. Recommendations are given for the effect of non-condensable gasesrnconcentrations on the length of horizontal tubes for air-cooled ammonia condensers.
机译:用于氨气终端的大容量制冷系统的运行条件受到进入冷凝器的不可冷凝气体的强烈影响。进行了高浓度不凝性气体风冷冷凝器运行的实验研究。确定了不凝性气体对水平管内氨气凝结的影响特征。给出了在水平管内有空气的情况下,氨气冷凝的各种速度的各种数学模型的进一步结果。给出了关于非冷凝气体浓度对风冷氨冷凝器水平管长度的影响的建议。