HE II TWO PHASE FLOW IN AN INCLINABLE 22 m LONG LINE

机译:沿一条22 m长线的两相流

获取原文

摘要

In the line of previous work done at CEA Grenoble, large size experiments were performed with the support of CERN for the validation of the LHC two phase superfluid helium cooling scheme. In order to be as close as possible to the real configuration, a straight, inclinable 22 m long line of 40 mm I.D. was built. Very accurate measurements of temperatures and pressures obtained after in situ re-calibration and verified by independent sensors allowed us to validate our two-phase flow model. Although we focus on pressure losses and heat exchange results in relation to power injected, additional measurements such as quality, void fraction, and total mass flow rate enable a complete description of the two-phase flow. Experiments were carried out to cover the whole range of the future LHC He Ⅱ two-phase flow heat exchanger pipe: slope between 0 and 2.8 %, temperature between 1.8 and 2 K, total mass flow rate up to 7.5 g/s. Results confirm the validity of choice for the LHC cooling scheme.
机译:按照先前在CEA格勒诺布尔所做的工作,在CERN的支持下进行了大型实验,以验证LHC两相超流氦冷却方案。为了尽可能接近实际配置,请使用一条内径为40 mm的22 m长的直线直线。被建。原位重新校准后获得的非常精确的温度和压力测量值,并通过独立的传感器进行了验证,这使我们能够验证两相流模型。尽管我们专注于与注入的功率有关的压力损失和热交换结果,但是诸如质量,空隙率和总质量流率之类的其他测量值可以完整描述两相流。实验涵盖了未来的LHC HeⅡ两相流换热器的整个范围:斜率在0%至2.8%之间,温度在1.8%至2K之间,总质量流量高达7.5 g / s。结果证实了LHC冷却方案选择的有效性。