【24h】

Study on Condensation Features of Radiant Cooling Ceiling

机译:辐射冷却天花板的冷凝特性研究

获取原文
获取原文并翻译 | 示例

摘要

This paper studies the condensation features of radiant panel by means of experiment and simulation.The temperature of radiant panels and relative humidity of the attached layer are tested and their effect on condensation time is analysed,in the start-up stage.In stable stage,the impact of wet source features on the condensation time is analyzed using numerical calculation method.The results show that,in the start-up stage,the condensation occurs 6min after the starting.In the start-up stage the surface temperature of radiant decrease quickly.With the increasing of radiant temperature decrease rate,the condensations occur on the panel in advanced.So special attention should be paid on the surface temperature and effective measures should be taken to prevent condensation.In the stable stage,with the increasing of moisture diffusion rate the condensation occurs in advance but the advanced rate of time decreases accordingly.The panel which is above the wet source was the first to occur dews.Condensation time is proportional to the distance between radiant panel and wet source.And the proportion decreases with the moisture diffusion rate increasing.Therefore,in order to prevent condensation in the stable stage,the temperature of the panel which is above the wet source must be tested and controlled.
机译:本文通过实验和仿真的方法研究了辐射板的冷凝特性。在启动阶段测试了辐射板的温度和附着层的相对湿度,并分析了它们对冷凝时间的影响。利用数值计算方法分析了湿源特性对凝结时间的影响。结果表明,在启动阶段,冷凝水在启动后6min发生。在启动阶段,辐射表面温度迅速下降。随着辐射温度下降率的增加,面板上会逐渐产生冷凝水,因此应特别注意表面温度并采取有效措施防止冷凝水。在稳定阶段,随着水分扩散的增加率先发生凝结,但提前的时间率相应降低。湿源上方的面板最先发生ws。冷凝时间与辐射板与湿源之间的距离成正比,并且随着水分扩散速率的增加而减小,因此,为了防止在稳定阶段发生冷凝,湿源上方的板温度必须经过测试和控制。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号