INDOOR AIR QUALITY AND THE ADEQUACY OF CLEANING IN 25 FINNISH SCHOOLS

机译:25个芬兰学校的室内空气质量和清洁度

获取原文
获取原文并翻译 | 示例

摘要

Indoor air quality and the adequacy of cleaning were studied in 25 schools in a Finnish city. Methods included a questionnaire for teachers (Oerebro MM-40-FIN) and measurements of ventilation rate, CO_2, temperature, particulate matter (PM) and surface dust in 56 classrooms. In most classrooms, ventilation rates did not fulfill the rate required by the Finnish building code. CO_2 concentrations were lowest in classrooms with mechanical ventilation and highest in classrooms with natural ventilation. Ventilation rates correlated with PM in all particle size groups except the smallest one. Total PM-levels exceeded the recommended values, and almost all classrooms were too warm. No correlation was found between PM and surface dust. According to the questionnaire (n=424 teachers), main problems in the working environment were dust, stuffy or dry air and noise. There was a statistically significant correlation between perceived indoor air quality and symptoms. The prevalence of symptoms did not explain dissatisfaction with work.
机译:在芬兰城市的25所学校中研究了室内空气质量和清洁程度。方法包括对教师进行问卷调查(Oerebro MM-40-FIN),并测量56个教室的通风率,CO_2,温度,颗粒物(PM)和表面灰尘。在大多数教室中,通风率未达到芬兰建筑法规要求的通风率。机械通风教室的CO_2浓度最低,自然通风教室的CO_2浓度最高。除最小粒度组外,所有粒度组的通气率均与PM相关。总PM水平超过了建议值,几乎所有教室都太热了。在PM和表面粉尘之间未发现相关性。根据调查问卷(n = 424名教师),工作环境中的主要问题是灰尘,闷气或干燥的空气以及噪音。室内空气质量和症状之间在统计学上具有显着相关性。症状的流行不能解释对工作的不满。