We characterized the mixing of tracer gas in three fan systems under two airflow rate conditions. The systems were configured for 100% outside air and SF_6 gas was injected at a constant rate into the supply air stream. The tracer gas concentrations were measured using a GC/ECD. The downstream tracer gas mixing was evaluated by collecting samples from a 12 point sampling grid. Errors were calculated as the difference between the local and the average concentration divided by the average concentration. The maximum errors associated with central point sampling ranged from 0% to 14% and averaged 5.5%, while the errors associated with the 12 single point sampling locations ranged from 3% to 27% and averaged 11.2 %. Averaging of two sequential single samples did not significantly reduce errors. High and low flow rate data suggest that tracer gas mixing times of less than 6 seconds may result in higher errors.
机译:我们在两个气流速率条件下,将示踪气体在三个风扇系统中的混合特征化。该系统配置用于100%的外部空气,并且以恒定速率将SF_6气体注入到进气流中。使用GC / ECD测量示踪气体浓度。通过从12点采样网格收集样品来评估下游示踪气体的混合。误差计算为局部浓度与平均浓度之差除以平均浓度。与中心点采样相关的最大误差为0%至14%,平均为5.5%,而与12个单点采​​样位置相关的误差为3%至27%,平均为11.2%。对两个连续的单个样本求平均值不会显着减少误差。高和低流速数据表明示踪气体混合时间少于6秒可能导致更高的误差。