This investigation comparesrnperformance ratings obtained whenrntesting water-source heat pumps usingrnthe Air-Conditioning and RefrigerationrnInstitute (ARI) Standard 320 and thernInternational Organization forrnStandardization (ISO) Standard 13256-rn1. Multiple tests included a ducted 1.75rnkW (0.5 ton) unit and a non-ducted 3.52rnkW (1.0 ton) unit. Air external staticrnpressure and water flow were varied atrnthe ISO conditions to determine therncorrection in capacity and total powerrnmandated by the ISO standard. ISOrncooling capacity for the first and secondrnunits were 0.1 % higher and 1.1 % lowerrnthan the ARI capacity, respectively. ISOrncooling energy efficiency ratio (EER) forrnthe first and second units were 4.5 %rnhigher and 3.9 % lower than the ARIrnEER, respectively. ISO heating capacityrnfor the first and second units were 4.8 %rnlower and 2.9 % lower than the ARIrncapacity, respectively. ISO heatingrncoefficient of performance (COP) for thernfirst and second units were 6.2 % higherrnand 1.0 % lower than the ARI COP,rnrespectively.
机译:本研究比较了使用空调和制冷研究所(ARI)标准320和国际标准化组织(ISO)标准13256-rn1测试水源热泵时获得的性能等级。多项测试包括管道式1.75rnkW(0.5吨)装置和非管道式3.52rnkW(1.0吨)装置。在ISO条件下改变空气的外部静压力和水流量,以确定由ISO标准规定的容量和总功率的校正。第一和第二单元的ISO制冷量分别比ARI容量高0.1%和低1.1%。第一和第二单元的ISO制冷能效比(EER)分别比ARIrnEER高4.5%和3.9%。第一单元和第二单元的ISO加热能力分别比ARIrn能力低4.8%和2.9%。第一和第二单元的ISO加热性能系数(COP)分别比ARI COP高6.2%和低1.0%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号