首页> 外文会议>The 3rd Technical Symposium on Computer Applications in Fire Protection Engineering, Sep 12-13, 2001, Baltimore, MD >An Analysis of the Installation of Open Panel Ceiling Designs on Sprinkler Response Time Using the NIST Fire Dynamics Simulator
【24h】

An Analysis of the Installation of Open Panel Ceiling Designs on Sprinkler Response Time Using the NIST Fire Dynamics Simulator

机译:使用NIST火灾动力学模拟器分析喷头响应时间上的开放式天花板设计的安装情况

获取原文
获取原文并翻译 | 示例

摘要

A sensitivity analysis was conducted to compare the sprinkler system response of an open panel ceiling configuration versus that of a conventional, smooth ceiling. The analysis is conducted using the NIST Fire Dynamics Simulator 1.0. The selected room is a large banquet hall located in a convention center. The symmetry of the layout has allowed a simulation of a subset of the space measuring 19.0 m x 6.53 m x 13.4 m high. This region was divided into approximately 110,000 grid cells. A series of 24 simulations were run. In each simulation the number of sprinklers that activate is between three and seven, with most simulations resulting in the activation of five sprinklers. In nearly all cases the sprinklers operate faster in the open panel configuration.
机译:进行了灵敏度分析,以比较开放式面板天花板配置与传统光滑天花板之间的洒水系统响应。使用NIST Fire Dynamics Simulator 1.0进行分析。选定的房间是位于会议中心的大型宴会厅。布局的对称性允许模拟19.0 m x 6.53 m x 13.4 m高的空间子集。该区域分为大约110,000个网格单元。运行了一系列的24个模拟。在每个模拟中,激活的喷头数量在3到7之间,大多数模拟会激活5个喷头。在几乎所有情况下,洒水喷头在开放式面板配置中的运行速度都更快。