首页> 外文会议>3rd IET International Conference on Clean Energy and Technology >Analysis of ferroresonance suppression and transient response performances for various ferroresonance suppression circuits in capacitive voltage transformers
【24h】

Analysis of ferroresonance suppression and transient response performances for various ferroresonance suppression circuits in capacitive voltage transformers

机译:电容式电压互感器中各种铁磁谐振抑制电路的铁磁谐振抑制和瞬态响应性能分析

获取原文
获取原文并翻译 | 示例

摘要

This paper presents the analysis of various ferroresonance suppression circuits (FSCs) in 132 KV Capacitive Voltage Transformers (CVTs). Simulation studies are conducted on 132 kV Trench CVT using Electro-Magnetic Transients Program (EMTP). In this paper, ferroresonance is initiated in CVT by circuit breaker switching. The ferroresonance mitigation performances of these FSC methods are then evaluated and compared. In addition, the transient response of the CVT due to power system fault is also investigated for the different types of FSC circuits. It is demonstrated in this paper that, the transient performance of CVT with electronic type FSC delivered the best results in comparison to active or passive ferroresonance mitigation circuits.
机译:本文介绍了132 KV电容式电压互感器(CVT)中各种铁磁谐振抑制电路(FSC)的分析。使用电磁暂态程序(EMTP)对132 kV沟槽式CVT进行了仿真研究。本文通过断路器开关在CVT中启动铁磁谐振。然后评估和比较这些FSC方法的防恐怖效果。此外,对于不同类型的FSC电路,还研究了由于电力系统故障引起的CVT的瞬态响应。本文证明,与有源或无源铁磁谐振缓解电路相比,带电子FSC的CVT的瞬态性能提供了最佳结果。