首页> 外文会议>2018 IEEE/IAS 54th Industrial and Commercial Power Systems Technical Conference >Heat generation and failure in padmount transformers due to zero sequence saturation
【24h】

Heat generation and failure in padmount transformers due to zero sequence saturation

机译:零序饱和导致发热和焊盘式变压器故障

获取原文
获取原文并翻译 | 示例

摘要

After a transformer failed following a double phase fault, there was an interest in understanding how the fault mechanism led to the failure. This paper investigate this fault condition in detail and demonstrate the underlying challenges in correcting the failure. The system electrical and thermal models were developed and simulated to analyze the transformer response under double phase fault conditions. Experimental measurements validated the simulation results on a real three phase distribution transformer. This paper presents the results from simulated and experimental analysis from double phase fault on a Yg-Yg distribution transformer.
机译:在变压器因双相故障而发生故障后,有兴趣了解故障机制是如何导致故障的。本文详细研究了这种故障情况,并说明了纠正故障的潜在挑战。开发并仿真了系统电气模型和热模型,以分析双相故障条件下的变压器响应。实验测量结果验证了实际三相配电变压器上的仿真结果。本文介绍了Yg-Yg配电变压器双相故障的模拟和实验分析结果。