首页> 外文会议>2018 IEEE International Conference on Industrial Electronics for Sustainable Energy Systems >Detection of high impedance faults in PV systems using mathematical morphology
【24h】

Detection of high impedance faults in PV systems using mathematical morphology

机译:使用数学形态学检测光伏系统中的高阻抗故障

获取原文
获取原文并翻译 | 示例

摘要

Use of Mathematical Morphology (MM) based filters to detect faults in power systems have been discussed in recent literature. These studies have been predominantly focused on AC systems and associated arc faults. However, fault detection applications based on MM filtering in DC systems have not been adequately discussed. This paper presents how MM based filtering techniques and its composite operations could be used to successfully detect arc faults in a PV system. Throughout the analysis, series and parallel arc fault signatures obtained from an actual PV system with maximum power point tracking (MPPT) control is used. Effect of MM parameters on detection sensitivity is explained.
机译:在最近的文献中已经讨论了使用基于数学形态学(MM)的滤波器来检测电力系统中的故障。这些研究主要集中在交流系统和相关的电弧故障上。但是,在DC系统中基于MM滤波的故障检测应用尚未得到充分讨论。本文介绍了如何将基于MM的滤波技术及其组合操作用于成功检测光伏系统中的电弧故障。在整个分析过程中,使用了从具有最大功率点跟踪(MPPT)控制的实际光伏系统获得的串联和并联电弧故障信号。解释了MM参数对检测灵敏度的影响。