Investigating reflections and refractions effects in the UHF Location of partial discharges in power transformers using time domain simulation

机译:使用时域仿真研究电力变压器局部放电在UHF位置的反射和折射效应

获取原文
获取原文并翻译 | 示例

摘要

The measurement of Ultra High Frequency (UHF) electromagnetic waves originated from a partial discharge (PD) source has been used for the identification and location of defects in power transformers. This method is based on the time-difference-of-arrival (TDOA) of the PD electromagnetic radiation using UHF sensors installed on the transformer. Then, it is possible to estimate the original position of the measured signals. However, it is known that the propagation of electromagnetic waves is affected by the reflections and refractions that occur inside the transformer, causing delays in propagation time and generating errors in the localization algorithms. For this reason, the refractions and reflections of the PD radiation on power transformers was studied in order to evaluate their effects on the delay of the signals arrival time. For this, the CST Microwave was used to simulate a power transformer model and to evaluate the effects of the core and windings in the wave propagation. Finally, the PD source was located from the measured signals and the error in the original source location was evaluated.
机译:来自局部放电(PD)源的超高频(UHF)电磁波的测量已用于识别和定位电力变压器中的缺陷。该方法基于使用安装在变压器上的UHF传感器的PD电磁辐射的到达时间差(TDOA)。然后,可以估计测量信号的原始位置。然而,众所周知,电磁波的传播受到变压器内部发生的反射和折射的影响,从而导致传播时间的延迟并在定位算法中产生误差。因此,研究了PD辐射在电力变压器上的折射和反射,以评估其对信号到达时间延迟的影响。为此,使用CST微波来模拟电力变压器模型并评估铁芯和绕组在波传播中的影响。最后,从测量信号中找到PD源,并评估原始源位置中的误差。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号