Sub-Cyclic Damaging Ferroresonant Overvoltages in 230 kV Transmission Systems Field Experience of 230 kV Transformer-Ended Cable Feeders Failure

机译:230 kV输电系统中的亚循环破坏性铁磁过电压230 kV变压器端电缆馈线故障的现场经验

获取原文
获取原文并翻译 | 示例

摘要

Extensive research and world-class standards have reported the ferroresonance phenomenon as a low-frequency temporary overvoltage with a range of voltage shape starting from 1 cycle. This paper provides a case study for a typical 230 kV transformer-ended cable feeder configuration that has experienced damaging ferroresonant overvoltages in 3/4 cycle. Ferroresonant overvoltages were recorded in two (2) different incidents and a similar 230 kV feeder configuration with magnitudes exceeding 2.75 pu in 12 ms causing a phase insulation breakdown in power transformers and a longitudinal insulation breakdown in circuit breakers. Waveform records captured at 32 samples per cycle are analyzed and used to validate a PSCAD/EMTDC model. Trigger mechanisms of this sub-cyclic ferroresonance profile are identified and preventive/protective measures are discussed based on recommendations for IEEE and IEC standards.
机译:广泛的研究和世界一流的标准已经将铁磁谐振现象报告为低频暂时性过电压,其电压形状范围从1个周期开始。本文提供了一个典型的230 kV变压器端电缆馈线配置的案例研究,该配置在3/4周期内遭受了破坏性的铁磁过电压。在两(2)次不同事件中记录了铁磁过电压,并且在12毫秒内记录了相似的230 kV馈线配置,其幅值超过2.75 pu,从而导致电力变压器的相绝缘击穿和断路器的纵向绝缘击穿。分析每个周期以32个样本捕获的波形记录,并将其用于验证PSCAD / EMTDC模型。根据针对IEEE和IEC标准的建议,确定了该亚周期铁磁谐振曲线的触发机制,并讨论了预防/保护措施。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号