In recent years, insulating tubular bus-bar has been widely used in power systems for its excellent electrical performance. However, as some new electrical equipment, there is still no unified principle at home and abroad, and little research is done on its operating characteristics. This leads to a confused market, and some abnormal operating phenomena appear in operation. In this paper, a 35kV insulating tubular bus-bar which operates abnormally in a substation is studied. According to the disintegration phenomena, experiment and simulation results, we have a suspicion that the abnormal phenomena is caused by the unreasonable match between semi-conducting layer and metal shielding layer. As the semi-conducting layer is weak in electric strength and inflammable, this defect develops quickly into bulging, smoking and burning when partial discharge appears. Besides, some methods to evaluate tubular bus-bar after the handover tests is proposed, and online detections, such as infrared temperature measurement, high frequency partial discharge, are recommended in daily inspection and maintenance.
机译:近年来,绝缘管状汇流排以其出色的电气性能而被广泛用于电力系统。但是,作为一些新的电气设备,国内外仍然没有统一的原则,对其工作特性的研究很少。这导致市场混乱,并且在操作中出现一些异常的操作现象。本文研究了35kV变电站绝缘管状母线。根据崩解现象,实验和仿真结果,我们怀疑异常现象是由半导体层和金属屏蔽层之间不合理的匹配引起的。由于半导体层的电强度弱并且易燃,因此当出现局部放电时,该缺陷会迅速发展为鼓胀,冒烟和燃烧。此外,提出了一些移交测试后评估管状母线的方法,并建议在日常检查和维护中进行在线检测,例如红外温度测量,高频局部放电。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号