Studying the fault power cable shielded plug-type uncharged separable connector, considering the construction technology, design technology and material properties, the tests were designed for the sample to find out the reasons. With the compare of the size verification between the connector tested and mainstream products, the advantages and disadvantages of the connector tested could be acquired. Then electrical tests on the sample were done to verify the electrical performance of the sample. Firstly, withstand-voltage test and partial discharge test were studied for detect the connector main insulation. Secondly, the shield resistance and shielding leakage current test were designed to study the semi-conductive performance. Thirdly, testing the shield resistance after aging, the performance of connector running for a long time was analyzed. Finally, using moist air to simulate the operating environment, the shield leakage current was test to judge the product performance. According to the tests, the reasons of the shielded plug-type uncharged separable connector fault could be found.
机译:在研究故障电缆屏蔽的插头式无电可分离连接器的基础上,结合施工技术,设计技术和材料性能,设计了测试样本,以找出原因。通过比较被测连接器和主流产品的尺寸验证,可以了解被测连接器的优缺点。然后对样品进行电学测试以验证样品的电性能。首先,研究了耐压测试和局部放电测试以检测连接器的主要绝缘。其次,设计屏蔽电阻和屏蔽漏电流测试来研究半导体性能。第三,测试老化后的屏蔽电阻,分析了长时间运行的连接器的性能。最后,使用潮湿的空气模拟操作环境,测试屏蔽泄漏电流以判断产品性能。根据测试,可以找到屏蔽插头式不带电可分离连接器故障的原因。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号