When faults occur on the circuit to which the distributed generation (DG) is connected, the circuit breaker of power distribution system trips the faulted circuit, and forms DG islanding. This paper examines the performance of anti-islanding protection based on asymmetric tripping of feeder circuit breaker under fault scenarios. Considering that the protection relay equipped by DG such as overcurrent protection is responsible for the fault to trip the DG, an effectively grounded medium-voltage distribution network with synchronous DG interconnection is employed to test the performance of anti-islanding protection with overcurrent protection. Simulation results show that under fault scenarios, the anti-islanding protection does not mal-operate and the overcurrent protection will trip the fault correctly.
机译:当分布式发电(DG)连接的电路上发生故障时,配电系统的断路器会使故障电路跳闸,并形成DG孤岛。本文研究了在故障情况下基于馈线断路器非对称跳闸的防孤岛保护的性能。考虑到由DG配备的保护继电器(例如过流保护)是导致DG跳闸的原因,因此,采用有效接地的,具有同步DG互连的中压配电网来测试具有过流保护的防孤岛保护的性能。仿真结果表明,在故障情况下,防孤岛保护不会发生误动作,过电流保护将使故障正确跳闸。