首页> 外文会议>2015 IEEE Power amp; Energy Society General Meeting >Experimental Transient Stability Analysis of MicroGrid systems: Lessons learned
【24h】

Experimental Transient Stability Analysis of MicroGrid systems: Lessons learned

机译:MicroGrid系统的实验瞬态稳定性分析:经验教训

获取原文
获取原文并翻译 | 示例

摘要

A Transient Stability Analysis of a low inertia microgrid system is presented in this paper. The analysis is performed on experimental data collected for different case scenarios of grid disturbances. The test bed consists of a reconfigurable 100kW MicroGrid system with more than 10 rotating generators, PV, and Wind penetration capabilities. Both islanded and non-islanded situations are considered for a solid three phase fault analysis and comparison. The paper also presents the results of fault scenario when the rotating machines are pushed to an unstable region. The experimental results and system behavior observed show interesting phenomena. The MicroGrid showed higher resiliency for faults than expected even if the relative angles are more than 160° and even if the fault is sustained for a long time.
机译:本文提出了低惯性微电网系统的暂态稳定性分析。分析是针对针对电网干扰的不同案例场景收集的实验数据进行的。测试台由可重构的100kW MicroGrid系统组成,该系统具有10多个旋转发电机,PV和防风能力。对于独立的三相故障分析和比较,均应考虑孤岛和非孤岛的情况。本文还介绍了将旋转电机推至不稳定区域时的故障情况结果。观察到的实验结果和系统行为显示出有趣的现象。即使相对角度大于160°,即使故障持续很长时间,MicroGrid也会显示出比预期更高的故障弹性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号