首页> 外文会议>2015 IEEE First International Conference on Direct Current Microgrids >Phase-lock loop of Grid-connected Voltage Source Converter under non-ideal grid condition
【24h】

Phase-lock loop of Grid-connected Voltage Source Converter under non-ideal grid condition

机译:非理想电网条件下并网电压源变换器的锁相环

获取原文
获取原文并翻译 | 示例

摘要

It is a normal practice that the DC micro-grid is connected to AC main grid through Grid-connected Voltage Source Converter (G-VSC) for voltage support. Accurate control of DC micro-grid voltage is difficult for G-VSC under unbalanced grid condition as the fundamental positive-sequence component phase information cannot be accurately tracked. Based on analysis of the cause of double-frequency ripple when unbalance exists in main grid, a phase-locked loop (PLL) detection technique is proposed. Under the conditions of unsymmetrical system voltage, varying system frequency, single-phase system and distorted system voltage the proposed PLL can accurately detect the fundamental positive-sequence component of grid voltage thus accurate control of DC micro-grid voltage can be realized.
机译:通常的做法是,将直流微电网通过并网电压源转换器(G-VSC)连接到交流主电网以提供电压支持。对于G-VSC,在不平衡电网条件下,DC微电网电压的精确控制非常困难,因为无法精确跟踪基本的正序分量相位信息。在分析主电网不平衡时产生双频纹波的原因时,提出了一种锁相环(PLL)检测技术。在系统电压不对称,系统频率变化,单相系统和系统电压失真的情况下,所提出的锁相环可以准确地检测出电网电压的基本正序分量,从而可以实现对直流微电网电压的精确控制。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号