首页> 外文会议>2015 IEEE 11th International Conference on the Properties and applications of Dielectric Materials >Calculating model of insulation life loss of dry- type transformer based on the hot-spot temperature
【24h】

Calculating model of insulation life loss of dry- type transformer based on the hot-spot temperature

机译:基于热点温度的干式变压器绝缘寿命损失计算模型

获取原文
获取原文并翻译 | 示例

摘要

The mechanism of thermogenesis and thermolysis of transformer was analyzed in this paper, the position of the hot-spot temperature was also analyzed. By calculating winding average surface temperature rising, a hot-spot temperature calculating model of dry -type transformer was established, and the calculating model of insulation life loss of dry-type transformer was established based on the hot-spot temperature calculating model. In the end, according to a practical example, the winding hot-spot temperature was calculated, the ageing rate of transformer winding under rated load was calculated by the calculating model, and the insulation life loss of the transformer was evaluated. The result shows that the hot-spot temperature of LV coil is higher than HV coil; the winding has a smaller aging rate and insulation life loss when less than rated load.
机译:分析了变压器的生热和热解机理,并分析了热点温度的位置。通过计算绕组平均表面温升,建立干式变压器的热点温度计算模型,并根据热点温度计算模型建立干式变压器的绝缘寿命损失计算模型。最后,根据一个实际的例子,计算了绕组的热点温度,通过计算模型计算了变压器在额定负载下的老化率,并评估了变压器的绝缘寿命损失。结果表明,低压线圈的热点温度高于高压线圈。小于额定负载时,绕组的老化率和绝缘寿命损失较小。