摘要

Double-circuit transmission lines are usually untransposed within short distance, in which case the fault characteristics will be significantly different from the ideal transposition cases. In this paper, based on the analysis of fault characteristics of the untransposed double-circuit transmission lines on the same tower, a practical fault phase selection scheme is proposed to identify various fault types. Firstly, on the base of six-sequence component, the voltage, current and phase angle information are used to classify the faults into single line faults, same phase cross-county faults and different phase cross-county faults. Then, for each of the three categories, the specific fault phase is selected according to the current phase information. The simulation results of PSCAD given in this paper illustrate that the scheme proposed can withstand a greater degree of asymmetry of lines and identify all the fault types accurately.
机译:双回路传输线通常在短距离内不进行换位,在这种情况下,故障特性将与理想的换位情况明显不同。本文在分析同一座塔上未换位双回线故障特征的基础上,提出了一种实用的故障选相方案来识别各种故障类型。首先,在六序分量的基础上,利用电压,电流和相角信息将故障分为单线故障,同相跨县故障和不同相跨县故障。然后,针对三个类别中的每个类别,根据当前阶段信息选择特定故障阶段。本文给出的PSCAD仿真结果表明,所提出的方案能够承受更大程度的线路不对称性,并能准确识别所有故障类型。