The paper presents the results of experimental and computational investigations of power quality in the 10 kV network with different types of neutral grounding. It is shown that parameters of equipment, connected to the neutral point, have a significant impact on power quality in the field of voltage unbalance, up to deviation from standard values. The area of proper power quality in the field of zero sequence voltage unbalance for 10 kV network is determined. It depends on the ratio of overhead lines and cable lines capacitive current, on the type of neutral grounding. It is found out that power quality in the field of zero sequence voltage unbalance may be significantly improved by connection of additional resistance into a zero sequence circuit of the network.
机译:本文介绍了采用不同类型中性点接地的10 kV网络中电能质量的实验和计算研究结果。结果表明,连接到中性点的设备参数对电压不平衡领域中的电能质量有很大影响,直到偏离标准值为止。确定了10 kV网络零序电压不平衡领域中合适的电能质量区域。它取决于架空线和电缆线电容性电流的比率,取决于中性点接地的类型。已经发现,通过将附加电阻连接到网络的零序电路中,可以显着改善零序电压不平衡领域的电能质量。