首页> 外文会议>2013 International conference on information business and education technology >Simulation and Analysis of DC Current Distribution in AC Power Grid around the UHVDC Transmission Ground Electrode
【24h】

Simulation and Analysis of DC Current Distribution in AC Power Grid around the UHVDC Transmission Ground Electrode

机译:特高压直流输电地电极周围交流电网直流电流分布的仿真分析

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

Due to the DC bias of the neutral earthed transformers caused bv UHVDC earthreturn current,it's very important to study the DC current distribution in AC power grid.Based on the±800kV Xiangjiaba-Shanghai UHVDC power transmission project,this paper simulates the DC Current distribution in Northern Zhejiang Ac grid by establishing a complete model based on the actual power grid and soil data inCDEGS.By the comparison of the simulation values and measured values,the validity of the model is verified.At last,a proposal is put torward to restrain DC current distribution in Northern Zhejiang AC grid.
机译:由于中性点接地变压器的直流偏置会引起UHVDC接地回路电流,因此研究交流电网中的直流电流分布非常重要。本文基于±800kV向家坝—上海特高压直流输电工程,模拟了直流电流的分布。通过在CDEGS中基于实际电网和土壤数据建立一个完整的模型,在浙北Ac电网中进行了仿真和实测值比较,验证了模型的有效性。浙北交流电网的直流电流分布。