Comparison of insulation states between new and operated EHV XLPE cables

机译:新的和运行的EHV XLPE电缆之间的绝缘状态比较

获取原文
获取原文并翻译 | 示例

摘要

Analysis of high voltage out of service cables elucidates the state of cable insulation after several years of operation. Operated cables are obtained from the Beijing state grid, China. The characteristic of the electrical tree growth and the corresponding partial discharge (PD) of cross-linked polyethylene slices at 11kV and 13kV are simultaneously monitored. Morphology structures of these slices are examined by differential scanning calorimetry (DSC), thermogravimetry (TG), Fourier transform infrared spectroscopy (FTIR) and mechanical property analysis. Results of the electrical tree experiment show that new and operated cables have similar electrical tree shapes; Operated cables have shorter initiation time, and larger PD magnitude than new cables. DSC results indicate that the left limit temperature of the melting peak for operated cables decreases relative to that of the new cables, and the crystallization rate increases. Thermal stability analysis by TG and FTIR indicate almost no change to operated samples except for one exhibiting a certain extent of thermal oxidation aging. Statistical mechanical property parameters of operated cable are within the normal range.
机译:对停止运行的电缆中的高压进行分析,可以阐明运行几年后电缆的绝缘状态。可从中国北京国家电网获得可操作的电缆。同时监测11kV和13kV交联聚乙烯切片的电树生长特性和相应的局部放电(PD)。通过差示扫描量热法(DSC),热重法(TG),傅立叶变换红外光谱法(FTIR)和机械性能分析来检查这些切片的形态结构。电气树实验的结果表明,新的和运行的电缆具有相似的电气树形状;操作的电缆与新电缆相比,具有较短的启动时间和更大的PD幅值。 DSC结果表明,相对于新电缆,操作电缆的熔化峰的左极限温度降低,并且结晶速率增加。 TG和FTIR的热稳定性分析表明,操作样品几乎没有变化,只是样品表现出一定程度的热氧化老化。工作电缆的统计机械性能参数在正常范围内。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号