Microgrid unbalance compensator - Mitigating the negative effects of unbalanced microgrid operation

机译:微电网不平衡补偿器-缓解微电网不平衡运行带来的负面影响

获取原文
获取原文并翻译 | 示例

摘要

A shunt connected three-phase four-leg power electronic-based compensator is proposed which allows the microgrid to behave as a “good citizen” from the viewpoint of the utility even though the microgrid itself is operating under highly unbalanced conditions. The same compensator when interfaced to a synchronous generator-based micro-generation unit can also be utilized to significantly reduce the double system frequency (100 Hz) power oscillation component arising due to unbalanced loading which can accelerate generator wear. This paper presents the compensation strategies, control algorithm and structure of the compensator. In addition, experimental results are presented which validate the compensator design.
机译:提出了一种基于并联连接的三相四臂电力电子补偿器,即使微电网本身在高度不平衡的条件下运行,该微电网也可以从公用设施的角度充当“良好公民”。当连接到基于同步发电机的微型发电机单元时,相同的补偿器也可用于显着降低由于负载不平衡而导致的双系统频率(100 Hz)功率振荡分量,这会加速发电机的磨损。本文介绍了补偿器的补偿策略,控制算法和结构。此外,还提供了验证补偿器设计的实验结果。